TITAN Grid Simulator AC

TITAN AC Grid Simulator

300kVA to 1MVA Unit Power, 10MVA Max. Parallel, Comprehensive Grid Emulation for Grid-Tied Equipment Validation


Defined by ActionPower as the tower-type high-power programmable AC power source, TITAN Grid Simulator features a high-power density of 209.5kVA per m2 and 107.1kVA per m3, with four-quadrant operation capability and regenerative load technology for validating utility-scale grid-forming and grid-following inverters, power conversion systems and miscellaneous of grid-tied and grid-support components among IEEE 1547 defined DERs.

User Manual

【User Manual】TITAN AC Series Grid Simulator CE Version

Detailed installation, operation procedures, and safety information for engineers.

Technical Specification

【Specification】TITAN Series AC Grid Simulator Non-CE Standard Version

Technical specification that provides full detailed introduction to TITAN grid simulator.

Technical Specification

【Specification】TITAN Series AC Grid Simulator CE Version

Technical specification that provides full detailed introduction to TITAN grid simulator.

CE-Certified Model Options

Model Power (kVA) Voltage Range (V) Frequency (Hz) Max. Current (A) Dimension (mm) Weight (kg)
TA300-576-033000-57640-703002410x1955x12002960
TA400-576-044000-57640-704002410x1955x12002960
TA500-576-055000-57640-705002410x1955x12002960
TA600-576-066000-57640-706003410x1955x14005300
TA700-576-077500-57640-707503410x1955x14005300

Standard Model Options (Non-CE)

Model Power (kVA) Voltage Range (V) Frequency (Hz) Max. Current (A) Dimension (mm) Weight (kg)
TA1K0-450-1610000-45040-7016006810x1955x14007720
TA1K0-700-1010000-70040-7010003410x1955x14005810
TA1K0-860-1010000-86040-7010003410x1955x14005810
TA300-450-053000-45040-705002410x1955x12002630
TA300-700-033000-70040-703002410x1955x12002560
TA300-860-033000-86040-703002410x1955x12002560
TA400-450-064000-45040-706002410x1955x12002920
TA400-700-044000-70040-704002410x1955x12002770
TA400-860-044000-86040-704002410x1955x12002770
TA500-450-085000-45040-708003410x1955x14003860

Technical Features

High-power tower-type AC source for utility-scale grid-tied equipment testing, with holistic grid emulation capability, built-in pre-compliance automated testing sequences, future-proofing scalability and energy-cost-saving regenerative load technology.


Source-Load Mode in Once Unit & 4-Quadrant Operation Capability

TITAN Grid Simulator's operation covers all 4 quadrants of I-V Cartesian system with automatic source-load switching capability to emulate either an AC source as if a real power grid or as an AC load to receive current from the DUT. Such a feature marks TITAN Grid Simulator the ideal grid connectivity and adaptability testing system for PV inverters, V2G, EV chargers, EVSE, Energy Storage Systems, UPS, and AC/DC converters.

TITAN Grid Simulator is with Four Quadrant Operation Capability

Regenerative Load Technology for Faster ROI and Saving Test Energy Cost

TITAN Grid Simulator, when operating as an AC load or sinking current from the DUT, is able to recover up to 94% efficiency the energy back into the utility mains instead of dissipating it as heat in the way a load bank works. The saved energy cost achieves significantly improved ROI to shorten your payback period after implementing the testing systems. You may also refer to our Regenerative Load ROI Calculator to calculate your ROI with regenerative grid simulators.

regenerative load saves energy cost for grid emulation testing

flexible test platform recomposition with parallel connection of grid simulator TITAN

Scalable Design to Reach 10MVA through Parallel or Series Connection

DMPS technology of ActionPower strikes the balance between high-power and consistency of response and dynamics while scaling up with TITAN grid simulator. Users or test engineers may set multiple set of TITAN in parallel connection for reaching 10 MVA without compromising performance. For matching shifting test requirements and user cases, multi-output mode is available to split a single 10MVA platform in to flexible combination of several sub-platform, supposing 3MVA + 4MVA + 4MVA and with multi-voltages, multi-station operation capability, as an example.


High Precision, Response and Dynamics for Emulating Transient Grid Anomalies

TITAN Grid Simulator features a fast voltage slew rage of 1V/μs and output of AC source with ultra-low distortion of THD no more than 0.5%. The system precisely replicates ranges of grid anomalies such as transient voltage interruption dynamically and accurately as if in real world scenarios.

waveform custom generation of grid simulator titan

versatile grid emulation capability of TITAN Grid Simulator

User-Defined Comprehensive Control Independently for Each Voltage Phase

TITAN allows independent phase control functions to emulate phase unbalance and shifts covering until 359.9° phase angel range with 0.1° resolution. Each of the 3 AC phases can be configured individually. Application emulation scenarios including phase change, frequency change, voltage change, phase split, etc.


User-Defined Harmonics & Inter-Harmonics Injection

The TITAN Grid Simulator provides extensive harmonic and interharmonic simulation capabilities for testing power electronics under distorted grid conditions. Harmonic Injection The simulator supports harmonic order generation up to the 50th order at both 50 Hz and 60 Hz. It allows precise synthesis of harmonic components with the following specifications:

  • 2nd–10th order harmonics: single harmonic content ≤ 40%, total harmonic distortion (THD) ≤ 60%.
  • 10th–20th order harmonics: single harmonic content ≤ 20%, THD ≤ 20%.
  • 21st–30th order harmonics: single harmonic ≤ 10%, total harmonics ≤ 10%.
  • 31st–50th order harmonics: single harmonic ≤ 5%, total harmonics ≤ 10%.
The amplitude accuracy of each harmonic component is within ±5% of the set value. A waveform preview function is available for verifying the synthesized harmonic distortion profile prior to output. The system supports harmonic waveform editing, including import, export, read, and storage of customized harmonic profiles. Interharmonic Simulation For interharmonic testing, the TITAN simulator supports a frequency range of 1 Hz to 2500 Hz with individual content up to 10%. Users can program up to 100 steps, each defined by parameters such as content, start frequency, end frequency, frequency increment, and execution time. The interharmonic programming interface supports flexible operations including add, delete, import, export, store, and read, enabling users to recreate complex and time-varying interharmonic conditions for compliance or stress testing.

harmonics distortion capability of TITAN grid simulator

voltage ride through LVRT and HVRT test capability of TITAN grid simulator

LVRT & HVRT / Low Voltage & High-Voltage Ride-Through Testing Application

Fast voltage and rise and fall time of 1ms together with the slew rate of 1V/μs, together with the phase control capability highlights TITAN Grid Simulator as the ideal AC source for conducting LVRT and HVRT testing applications in accordance to VDE-AR-N 4105 and other application standards against grid-tied DUTs.

User-Defined Waveform for Flicker Emulation

The TITAN Grid Simulator features built-in flicker simulation with ten selectable levels (1.0–10.0), a fine adjustment step of 1, and ±0.2 accuracy, enabling precise reproduction of voltage fluctuation effects. Engineers can preview flicker waveforms and visualize Pst trends in real time, facilitating verification and analysis. This function is widely used for evaluating the flicker emission and immunity of lighting equipment, inverters, and motor drives under dynamic grid conditions.

Technical Specifications

Note: The technical parameters contained within the below specification tables are subject to updates and modifications without notification in advance. For more detailed technical information please contact our sales and technical support team.

AC OUTPUT - VOLTAGE

Setting Resolution (V) 0.01
Accuracy ±0.1% F.S.
Wave Type Sine
DC Component (mV) <50
Voltage Distortion
  • Less than 0.5% @50Hz/60Hz > 220V for no-load
  • Less than 1% @50Hz/60Hz > 220V for linear load
  • Less than 1.0% @ other frequency > 220V for no-load
  • Less than 1.5% @ other frequency > 220V for linear load
Load Regulation ±0.1% F.S.
Line Regulation ±0.1% F.S. @ 10% variation
Voltage Slew Rate AC > 1.0V/μs
Dynamic Response <1ms (10%-90%Umax)

CURRENT & FREQUENCY

CURRENT
Accuracy ±0.1 F.S.
Resolution 0.01A
FREQUENCY
Accuracy ±0.01%
Resolution 0.001Hz
Range 40-70Hz

PHASE ANGLE & RIDE-THROUGH

PHASE ANGLE CONTROL
Accuracy / Resolution ±0.3° / ±0.1°
Range 0~359.9°
Phase Control Single-phase, Three-phase, Three-phase independent
VOLTAGE RIDE-THROUGH
Mode ZVRT / LVTR / HVRT
Setting Parameters Voltage, frequency, phase, rise time, hold time, trigger phase angle, pulse output

HARMONIC INJECTION

Cycles 50 cycles @ 50Hz, 50 cycles @ 60Hz
Content
  • Max 40% (2-10 single), <40% (2-10 total)
  • Max 20% (10-20 single), <20% (10-20 total)
  • Max 10% (21-30 single), <10% (total)
  • Max 5% (31-50 single), <5% (total)
  • Simultaneously synthesis 49 harmonics
Error / Range ±5% error / 0° ~ 359.9°
Features Waveform preview, Import/Export/Recall modes

GENERAL PROGRAMMING

Programming Mode List, Pulse, Step (100 steps)
Parameters per Step Voltage, Frequency, Phase, Transition/Hold Time, Trigger Phase/Pulse
Time Step / Range Min 100μs step; Range 100μs-999s
Trigger Source/Mode Local/External; Auto/Manual/External
Operation Mode Macro Cycle (1000) + Nested Programming (9999)

MEASUREMENT & INPUT

MEASUREMENT ACCURACY
Voltage / Frequency ±0.1% F.S. / ±0.01% F.S.
Current / Power ±0.2% F.S. / ±0.3% F.S. (Active & Apparent)
INPUT PARAMETERS
Wiring / Frequency 3pH+N+PE / 47-63Hz
Voltage / Power Factor 380V ±15% / 0.99

MISCELLANEOUS

Protection Input: OVP/UVP, Frequency, Phase Loss; Output: OVP/OCP/OPP, OTP
Interfaces Standard: LAN; Optional: RS485, CAN
Control & Display Local touchscreen & Remote PC monitoring; Real-time operational trends
Environment -10°C to +40°C; 10% to 90% RH; Altitude ≤2000m
Physical Forced air cooling; Noise ≤70dB; 3600VAC/1min dielectric strength

INTER-HARMONIC & FLICKERS

INTER-HARMONIC
Range / Steps 1Hz-3,000Hz (content <10%); 100 steps
FLICKERS (IEC 61000-3-3)
Level / Accuracy 1.0-10.0 (10 levels); Accuracy ±0.2
Functions One-key calling; Visualized PST trend preview